Electricity and Fluids (CONTAM Elementalization of Dampers)
1. Electrical
- V=IR
- R=ρL/A
2. Fluid
- Q=vA
- △P=ζ × Pd=ζ × 0.5ρv^2=ζ × 0.5ρ(Q/A)^2=(ζρ/A^2) × Q^2
- △P=R'Q^2 (R'=ζρ/A^2)
3. Electricity and fluids
- △P=R'Q^2
- V=IR
- V ≒ △P
- I ≒ Q^2
- R(ρL/A)≒ R'(ζρ/A^2)
4. CONTAM elementrization of the damper
- R' = ζρ/A^2
- Real: A=variable, ζ=variable
- CONTAM : Based on the performance test results (Q, △P, R') and full open cross-sectional area (A) of a specific damper --> Extract the maximum and minimum values of Terminal loss coefficient (ζ) to apply to the CONTAM program of a specific damper.
* Back to Main Procedures : General COMTAM Simulation Procedure for Pressure differential system(Mainly High-rise building) (contamsmulationlab.blogspot.com)